An ISO 9001 : 2008 Certified Company

Products

Online UPS iP11 Series

iP Series UPS System is a conventional type design with in-built isolation transformer based technology. iP series is known for its reliability during the long span of its operating life.

For their robust design, they are widely used in Industrial environment to meet the challenges the grid power supply. iP series is extensively employed in rural areas wherein the grid problems are higher and UPS has to withstand sustained power problems and longer outages.

Features

Specifications

iP SERIES iP-11 RANGE
PARAMETERS TECHNICAL DATA
MODEL iP1102 iP1103 iP1105 iP1106 iP1107
RATING 2KVA 3KVA 5KVA 6KVA 7.5KVA
INPUT VOLTAGE 230V,1 Phase,+10%, -15%
FREQUENCY 50 Hz + 5%
CHARGER TYPE Constant Voltage , Current Controlled (CVCC)
TECHNOLOGY IGBT based with PF > 0.9
DCV 72V 72V 120V 120/144V 180
OUTPUT VOLTAGE 230V + 1%, Single Phase
TECHNOLOGY IGBT based with PF > 0.9
FREQUENCY 50 Hz + 0.1%
WAVEFORM Sine wave with less than 2% voltage distortion on linear load
RATED PF 0.7 – 1
CREST FACTOR 3:1
USER INTERFACE METERING Input & Output and DC Voltage, DC current
INDICATION LED for Mains On , Mains Fail, Load on Battery, DC Over, Voltage, Inverter On,
Battery Low, Inverter Under/Over Voltage, Over Temperature
POTECTION DC Under / Over Voltage, DC Charging Current,
Output Under / Over Voltage, Short Circuit.
CABLE ENTRY Rear Bottom
ENVIRONMENT TEMPERATURE Operating: 0°c to 40°c, Storage: - 10°c to 65°c ; RH < 95%
ALTITUDE <1000 meters
PROTECTION DEGREE IP20
COOLING Forced Air
DIMENSIONS (in mm) Width × Depth 360 × 650       600 × 600
Height 900   1000 1275  
PAINT SHADE RAL – 7032
APPRX. WEIGHT (in Kgs) 175   225 275  

Contact Us