MP Series UPS System is a complete Industrial grade UPS system designed for supporting mission critical Process application. Machines, which are part of production process, are supported by MP33 series UPS of TechnoVision. MP-33 series UPS deals with challenging grid/Generator set environment like; surges, sags, blackout, frequency variations. MP-33 Provides uninterrupted Power quality power along with quality job output from the machines & prolonged equipment life.

MP-33 Series deploys Microcontroller based IGBT front end rectifier & IGBT based Inverter technology providing better power factor and operating efficiency. Time tested Technology Rugged design guarantee seamless operation and maximum ROI. Product is flexible enough to adopt to load profiles and necessary customization is possible.

Features

Specifications

MP SERIES  MP-33 RANGE
PARAMETERS TECHNICAL DATA
MODEL G7-3310 TO G7-33400
RATING (IN KVA) 10 - 20 30 - 40 60 - 80 100 - 120 160 - 250 300 -500
TOPOLOGY CONVERTER IGBT Based PWM Rectifier / Battery Charger with PF Control
INVERTER IGBT Based PWM Inverter
CONTROL Microcontroller Based Digital Control
ISOLATION Built-In Output Isolation Transformer for Galvanic isolation
INPUT

CONNECTION 3 Phase, 4 Wire
VOLTAGE 415V, +10%, -20%, Lowest operating voltage at -40%
FREQUENCY 50 Hz ± 10%
PF >0.99 @ Full Load
THD <5%
CHARGER

TYPE Constant Voltage, Current Controlled
DCV 240/300/360VDC
FLOAT CURRENT Options to set the current limit from 10% to 30% of the Battery AH
RIPPLE <2%
REGULATION ±1% @ INPUT Voltage Variation of ±10% and load Variation
POWER WALK IN 10 to 20 seconds
OUTPUT

RATED PF 0.8
VOLTAGE 415V ± 1%, Three Phase (Settable to 400V or 415V)
FREQUENCY 50 Hz ± 0.1%
WAVEFORM Pure Sine Wave
THD VOLTAGE < 1% on Linear Load and < 3% on Non Linear Load
CREST FACTOR 3:1
TRANSIENT Less than ±5% for a 20% to 100% load variation
RECOVERY Less than 15 msec
OVERLOAD Capability for 110% for 10 minutes, 125% for 5 minutes, 150% for 1 minute
EFFICIENCY   90% TO 96% Depending on the rating
USER INTERFACE

DISPLAY LCD with real time parameter display & fault signals as per occurance
INDICATION LED Indication for most of the events
INTERFACE Options of RS-232 /MODBUS/ Potential Free Contacts
PROTECTION INPUT : Under / Over voltage , Over Current
DC : Under / Over Voltage , Battery Charging current
OUTPUT : Under / Over Voltage , Over Load , Short Circuit
ENVIRONMENT

TEMPERATURE Operating: 0°c to 40°c, Storage: - 10°c to 65°c
HUMIDITY 0% - 95% Without condensation
ALTITUDE <1000 meters
PROTECTION DEGREE IP31
CABLE ENTRY Front Bottom/Top
COOLING Forced Air
PAINT SHADE RAL-7032 Siemens Grey (Structure Finish)